Project Description

Anti-static Laminate – HPL

Anti-static laminate is produced with original kraft paper, It’s an ideal application in floors for which high surface wear is necessary, and it’s the best use in the construction of access floors which can be installed on all types of floor, such as steel raised panel, calcium sulphate panel, woodcore panel, aluminum panel, etc.

Model: TT8001-TT8014

Thickness: 1.0-2.0mm

Size: 600*600mm

Application

Anti-static Laminate is widely used in varies computer rooms and data centers. It is anti-static, anti-wear and free of pollution

Characteristics

  • Special anti-static properties
  • Excellent resistance to wear and tear
  • Excellent resistance to scratching
  • Excellent chemical resistance
  • Easy to clean and maintenance

Test Parameter

Item

Standard

Data

Type of Floor Covering

EN649

Anti-static HPL

ASTM F 1700

Class III – Type B,

 High Pressure Laminate

NFPA Life sfty code 101

Class 1 – Interior Floor Finish

NFPA 99 Standard for health care facility

Meets Standard

Floor Classification

(Wear rating / Static load resistance)

EN 685

Commercial: 34 / Industrial: 43

No of Color

12

Tile Dimension Size

EN 42790° Press Cutting

600×600 / 610×610

ASTM F 536: Size Tolerance (<±0.4mm / 305mm)

< ±0.4mm / 305mm

Dimensional Stability

EN 434 /FED STD NO. 501a, M 6211

< 0.25%

ASTM F 540: Square Tolerance (<0.51mm / 305mm)

< 0.51mm / 305mm

Wear Layer Thickness

EN 429

0.30mm

Inter Layer

Print flim

Total Thickness

EN 428

1.20mm

ASTM F 386: Thickness Tolerance (±0.13mm)

Meets Standard

Weight / m2

EN 430

1.20mm: 0.5 kg/m2

Wear Resistance (Abrasion / Thickness Loss)

EN 660-1

< 0.08mm

EN 649

Group T

ASTM D 4060

(CS-17 Wheel, 1,000 g, 1,000 cycles)

70mg

Hardness

ASTM D 2240 (Type D)

67

Residual indentation

EN 433 / Din 51955

<0.04mm

ASTM F 1914 (<8%)

<8%

Static Load Limit

ASTM F 970

3,000 lbs/square inch; Long term

Flexibility

ASTM F 137

No Crack or Breaking

Castors Wheel test EN 425 No Damage
Electrical Resistance DIN 51953 / EN 1081 Anti-static 109 < R < 1012
ASTM F 150 / ESD F 7.1 / UL 779 Anti-static 1.0×109 ~ 1.0×1012

Critical Radiant Flux

ASTM E 648 / NFPA 253

Class 1 (1.08 w/cm2)

Flame Spread

ASTM E 162 / ASTM E 84 / NFPA 225

NFPA Class B / UBC Class II (<75)

Smoke Density

ASTM E 662 / NFPA 258

Passed (<450Dme)

Thermal Conductivity

DIN 52612 / NFX 10021

0.309 w/m.k

Underfloor Heating

DIN 52612

Suitable – Max 30℃

ASTM F 1514 (△E < 8 ave, max)

< △E = 8.0